Cummins

Cummins 110Kva Diesel Generator
Model Cummins - APS C110

Cummins 110kVA generator

Salient Features
Power:
bullet Prime Power @ 50Hz : 80kw/ 100kVA
bullet Stand By Power @ 50Hz : 88kw/110kVA
Features:
bullet Engine (Cummins 6BT5.9G2)
bullet Charge alternator 12V Governor: Mechanical
bullet Alternator (Stamford UCI274C)
bullet Single bearing alternator IP 23, insulation class H/H
bullet Radiator 50 C (122 F) max
bullet Skid and vibration isolators
bullet Dry type air filter
bullet Main line circuit breaker
bullet 12V battery, rack and cable
bullet Industrial silencer
bullet User manual
 
Engine Options:

Engine & Radiator:
bullet Heat shield protection
bullet Oil drain extension
bullet Heavy duty oil filter
bullet Lube oil drain pump
bullet Radiator core guard
bullet Battery charger
bullet Block header
Fuel:
bullet 24 hour day tank
bullet Bulk fuel tank connections
bullet Water separator fuel filter
Alternator:
bullet Anti-Condensation Heater
bullet Enforced impregnation
bullet Oversized alternator
Exhaust:
bullet Residential silencer
bullet Flexible exhaust connection
Enclosure:
bullet EM-1,5
bullet 83dba @ 1m silent canopy
Control Panel:
bullet Paralleling System
bullet Co-Map
bullet Remote annunciator
bullet Key start panel
Literature:
bullet Parts
bullet Maintenance
 
Engine Data
MANUFACTURER/MODEL Cummins 6BT5.9G2 PISTON SPEED 7.7 MS
CYLINDER ARRANGEMENT 6 inline Max. standby power at rated RPM 88 kW
DISPLACEMENT 5.9 L Frequency regulation, steady state +/- 2.5%
BORE AND STROKE 102.0 x 120 mm BMEP 5.62bar (81psi)
COMPRESSION RATIO 17.5:1 Governor: type Electronic
RATED RPM 1500Rpm    
Alternator Data
MANUFACTURER / TYPE Stamford UCI274C EXCITER TYPE NO
NUMBER OF PHASE 3 INSULATION: CLASS, TEMPERATURE RISE HH
POWER FACTOR COS PHI 0.8 VOLTAGE REGULATOR + / - 0.5%
ALTITUDE 1000 BEARING NUMBER 1 (AT NO LOAD)
OVER SPEED RPM COUPLING DIRECT
POLE: NUMBER 4 EFFICIENCIES @ 4/4 LOAD MS
Other Alternator Data
CONTINUOUS NOMINAL RATING @ 40 C 100kVA DIRECT AXIS TRANSIENT REACTANCE ATURATED (X'd) 18.5%
STANDBY RATING @ 27 C 110 kVA SHORT CIRCUIT TRANSIENT TIME CONSTANT (T'd) 18ms
EFFICIENCIES @ 4/4 LOAD 83.5% DIRECT AXIS SUBTRANSIENT REACTANCE SATURATED (X'd) 13.3%
AIR FLOW 3.5 m3/S (7416.05cfm) SUBTRANSIENT TIME CONSTANT (T'd) 12ms
SHORT CIRCUIT RATIO: 50 (Kcc) 0.78 QUADRA AXIS SUBTRANSIENT REACTANCE SATURATED (X'q) 72.7%
DIRECT AXIS SYNCHRO REACTANCE UNSATURATED (Xd) 206% ZERO SEQUENCE REACTACE UNSATURATED (Xo) 6.4%
QUADRA AXIS SYNCHRO REACTANCE UNSATURATED (Xq) 68% NEGATIVE SEQUENCE REACTANCE SATURATED (X2) 18.3%
OPEN CIRCUIT TIME CONSTANT: 50 (T'do) 0.78ms ARMATURE TIME CONSTANT (Ta) 13ms
NO LOAD EXCITATION CURRENT (io) A TRANSIENT DIP (4/4 CHARGE) - PF : 1.8AR %
FULL LOAD EXCITATION VOLTAGE (uc) A NO LOAD LOSSES N/A
RECOVERY TIME (DELTA U = 20% TRANSITOIRE) ms HEAT REJECTION kW
MOTOR START (DELTA = 20% PERM. OR 50% TRANS.) kVA    
Exhaust System
EXHAUST GAS FLOW 23.60L EXHAUST TEMPERATURE 490 C
Fuel System
110% (OF THE PRIME POWER) 35 L/H 100% (OF THE PRIME POWER) 22 L/H
75% (OF THE PRIME POWER) 17 L/H 50% (OF THE PRIME POWER) 11 L/H
Oil System
Total oil capacity w/filters 29dm3 Oil consumption 100% load <0.3g/kwh
Oil Pressure low idle 0.7bar Oil capacity carter 3.6L (1.0 gal)
Oil Pressure rated RPM 3-6 bar    
Thermal Balance
Heat rejection to exhaust 7kW (398 Btu/ mn) Heat rejection to coolant 8kw (455 Btu/ mn)
Radiated heat to ambient 0.5kW (28 Btu/ mn)    
Air Intake
MAX. INTAKE RESTRICTION COMBUSTION AIR FLOW: 310mm CE (12in WG) ENGINE AIR FLOW COOLING AIR FLOW: 9.9L/s (21cfm)
Coolant System
Radiator & engine capacity 20dm3 Fan air flow 4.3m3/s (848cfm)
Max water temperature 83-95C Available restriction on air flow 22mm CE
Outlet water temperature 93C (199F) Type of coolant Gen cool
Fan power 5kW Thermostat 76.5-90C
EMISSIONS
HC 30 mg/Nm3 Nox 960 mg/Nm3
CO 250 mg/Nm3 PM 120 mg/Nm3
Generator Ratings
VOLTAGE HZ PHASE P.F. STANDBY AMPS STAND BY RATINGS KW/KVA PRIME RATINGS KW/KVA
415/240 50 3 1 150 88/110 80/100
220/110 50 3 1 150 88/110 80/100
RRP: Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. A 10% overload capability is available for a period of 1 hour within 12hour period of operation, in accordance with ISO 3046-1.
ESP: The standby power rating is applicable for supplying emergency power in variable load applications i accordance with ISO 8528-1. Overload is not allowed