Model - Perkins – APS P100 |
 |
 |
Salient
Features
Power:
 |
Prime Power
@ 50Hz : 80 kW / 100 kVA |
 |
Stand By
Power @ 50Hz : 88 kW / 110 kVA |
Engine:
 |
Perkins,
1006-TG2A |
 |
6 Cylinder
in-line, Turbocharged |
 |
4 Stroke ,
Water cooled, direct fuel injection system |
 |
Cooling
Radiator & Fan |
 |
12V DC
Starter and Charging Alternator |
 |
Lead acid ,
Dry charged Starter Battery |
 |
Replaceable
Air , Fuel and Oil Filters |
 |
Developed
from heavy-duty industrial base therefore offering superior performance
and reliability |
 |
Diesel
engine which offers a choice of temperature or tropical cooling |
Alternator:
 |
Marelli,
MJB225MA4 |
 |
Self-excited
brushless , Single Bearing, Screen Protected & Drip Proof |
 |
Degree of
Protection IP 23 |
 |
Insulation
system, class H |
Control Module:
 |
Deepsea Electronics Model DSE 7210 |
Generating Set:
 |
Factory
tested to design specifications at full load conditions
|
 |
Fully
engineered with a range of options and accessories available
|
 |
Base mounted
fuel tank for 8 Hours Operation |
Literature:
 |
Operation
Manual |
 |
Electrical
Circuit Diagram
|
Optional Items:
Engine & Radiator:
 |
Heat shield
protection |
 |
Oil drain
extension & Pump |
 |
Heavy duty
oil filter |
 |
Radiator
core guard |
 |
Jacket Water
Heater |
Fuel System:
 |
Three Way
valve |
 |
Automatic
Fuel Filling System |
 |
Low Fuel
Level Alarm |
 |
Racor Fuel
water separator |
 |
Bulk fuel
tank & connections
|
Alternator:
 |
Enforced
impregnation |
 |
Anticondensation Heater |
 |
Oversized
alternator |
Exhaust:
 |
Residential
silencer |
 |
Sparker
Arrestor |
 |
Flexible
exhaust connection |
Enclosure:
 |
EM-1,5
|
 |
83dba @ 1m silent canopy |
Control Panel:
 |
ComAp , Dief
|
 |
Auto start
Control module |
 |
Paralleling
system |
 |
Remote
annunciator |
 |
Battery
Trickle Charger
|
|
Alternator Data |
MANUFACTURER / TYPE |
Marelli, MJB225MA4 |
INSULATION: CLASS,
TEMPERATURE RISE |
HH |
NUMBER OF PHASE |
3 |
VOLTAGE REGULATOR |
+ / - 0.5% |
POWER FACTOR COS PHI |
0.8 |
TOTAL HARMONICS (TGH/THC) |
< 2% (AT NO LOAD) |
OVER SPEED |
2250 MIN -1 |
EXCITER TYPE |
BRUSHLESS |
POLE: NUMBER |
4 |
EFFICIENCIES @ 4/4 LOAD |
FI Contact APS Staff |
|
Engine Data |
MANUFACTURER/MODEL |
Perkins, 1104C-44TAG2 |
COMPRESSION RATIO |
16 : 1 :1 |
CYLINDER ARRANGEMENT |
4 in-line, turbo charged |
RATED RPM |
1500 |
DISPLACEMENT |
5.99 LITRES |
PISTON SPEED |
9.5 M/S |
BORE AND STROKE |
105 mm x 127 mm |
BMEP |
2124 kpa |
|
Exhaust System |
EXHAUST GAS FLOW |
16.24
m³/min |
EXHAUST TEMPERATURE |
543 °C |
|
Fuel System |
100% (OF THE PRIME POWER) |
21.8 L/h |
75% (OF THE PRIME POWER) |
16.4 L/h |
50% (OF THE PRIME POWER) |
10.9 L/h |
|
|
|
Oil System |
Total
oil capacity w/filters |
16.1.0 Litres |
|
Air Intake |
MAX. INTAKE RESTRICTION |
COMBUSTION AIR FLOW: 110
m³/min |
ENGINE AIR FLOW |
COOLING AIR FLOW: 38
m³/min |
|
Coolant System |
RADIATOR & ENGINE CAPACITY |
MAX WATER TEMPERATURE |
CONTACT APS SALES TEAM FOR FURTHER INFORMATION |
|
Generator Ratings |
VOLTAGE |
HZ |
PHASE |
P.F. |
STANDBY AMPS |
STAND BY RATINGS
KW/KVA |
PRIME RATINGS
KW/KVA |
415/240 |
50 |
3 |
0.8 |
150 |
88 / 110 |
80 / 100 |
380/220 |
50 |
3 |
0.8 |
150 |
88 / 110 |
80 / 100 |
|
RRP: Prime Power is available
for an unlimited number of annual operating hours in variable load
applications, in accordance with ISO 8528-1. A 10% overload capability is
available for a period of 1 hour within 12hour period of operation, in
accordance with ISO 3046-1.
ESP: The standby power rating is applicable for supplying emergency power in
variable load applications in accordance with ISO 8528-1. Overload is not
allowed |
 |
Length (L) mm |
Width (W) mm |
Height (H) mm |
Dry kg (lb) |
Wet kg |
2089 |
1120 |
1367 |
1182 |
1200 |
Dry
= With Lube Oil |
Wet
= With Lube Oil and Coolant |
Ratings in
accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1/22.
Generating set pictured may include optional accessories. |
Fuel
consumption data at full load with diesel fuel with specific gravity of
0.85 and conforming to BS2869: 1998, Class A2. |
|