Perkins

APS Perkins 235KVA generator, UAE
Model - Perkins APS P235

Salient Features
Power:
Prime Power @ 50Hz : 188 kW / 235 kVA
Stand By Power @ 50Hz : 207 kW / 259 kVA
Engine:
Perkins, 1306C-E87TAG5
6 Cylinder in-line, Turbocharged
4 Stroke , Water cooled, direct fuel injection system
Cooling Radiator & Fan
24V DC Starter and Charging Alternator
Lead acid , Dry charged Starter Battery
Replaceable Air , Fuel and Oil Filters
Developed from heavy-duty industrial base therefore offering superior performance and reliability
Diesel engine which offers a choice of temperature or tropical cooling
Alternator:
Marelli, MJB250LB
Self-excited brushless , Single Bearing, Screen Protected & Drip Proof
Degree of Protection IP 23
Insulation system, class H
Control Module:
Deep-sea Electronics , Model DSE 7210
Generating Set:
Factory tested to design specifications at full load conditions
Fully engineered with a range of options and accessories available
Base mounted fuel tank for 8 Hours Operation
Literature:
Operation Manual
Electrical Circuit Diagram

Optional Items:

Engine & Radiator:
Heat shield protection
Oil drain extension & Pump
Heavy duty oil filter
Radiator core guard
Jacket Water Heater
Fuel System:
Three Way valve
Automatic Fuel Filling System
Low Fuel Level Alarm
Racor Fuel water separator
Bulk fuel tank & connections
Alternator:
Enforced impregnation
Anticondensation Heater
Oversized alternator
Exhaust:
Residential silencer
Sparker Arrestor
Flexible exhaust connection
Enclosure:
EM-1,5
83dba @ 1m silent canopy
Control Panel:
ComAp , Dief
Auto start Control module
Paralleling system
Remote annunciator
Battery Trickle Charger
 

Alternator Data

MANUFACTURER / TYPE

Marelli, MJB250LB

INSULATION: CLASS, TEMPERATURE RISE

HH

NUMBER OF PHASE

3

VOLTAGE REGULATOR

+ / - 0.5%

POWER FACTOR COS PHI

0.8

TOTAL HARMONICS (TGH/THC)

< 2% (AT NO LOAD) 

OVER SPEED

2250 MIN -1

EXCITER TYPE

BRUSHLESS

POLE: NUMBER

4

EFFICIENCIES @ 4/4 LOAD

FI Contact APS Staff

Engine Data

MANUFACTURER/MODEL

Perkins, 1306C-E87TAG5

COMPRESSION RATIO

16.9 : 1

CYLINDER ARRANGEMENT

6 in-line, turbo charged

RATED RPM

1500

DISPLACEMENT

8.7 LITRES

PISTON SPEED

9.5 M/S

BORE AND STROKE

116.6 mm x 135.9 mm

BMEP

2124 kpa

 

Exhaust System

EXHAUST GAS FLOW

29.40 m/min

EXHAUST TEMPERATURE

543 C

 

Fuel System

100% (OF THE PRIME POWER)

56.3 L/h

75% (OF THE PRIME POWER)

42.23 L/h

50% (OF THE PRIME POWER)

28.15 L/h

 

 

 

Oil System

Total oil capacity w/filters

26.4 Litres

 

Air Intake

MAX. INTAKE RESTRICTION

COMBUSTION AIR FLOW: 110 m/min

ENGINE AIR FLOW

COOLING AIR FLOW: 38 m/min

 

Coolant System

RADIATOR & ENGINE CAPACITY

MAX WATER TEMPERATURE

CONTACT APS SALES TEAM FOR FURTHER INFORMATION

 

Generator Ratings

VOLTAGE

HZ

PHASE

P.F.

STANDBY AMPS

STAND BY RATINGS KW/KVA

 

PRIME RATINGS KW/KVA

415/240

50

3

0.8

389

207 / 259

188 / 235

380/220

50

3

0.8

389

207 / 259

188 / 235

 
RRP: Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. A 10% overload capability is available for a period of 1 hour within 12hour period of operation, in accordance with ISO 3046-1.
ESP: The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is not allowed
Length (L) mm Width (W) mm Height (H) mm Dry kg (lb) Wet kg
2960 1003 1718 2100 2137
Dry = With Lube Oil
Wet = With Lube Oil and Coolant
Ratings in accordance with ISO 8528, ISO 3046, IEC 60034, BS5000 and NEMA MG-1/22. Generating set pictured may include optional accessories.
Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
website policy | sales terms & conditions | sitemap
Home | Generators | Perkins Range of Generators | Cummins Range of Generators | Fuel Storage Tanks | Cube tanks | Containerised fuel tanks | Self Bunded Fuel tanks | Lighting towers
Copyright 2015 Assosiated Power Solutions. All rights reserved.